Climate18 November 2026How much does AI weigh in a university's carbon footprint?
Use of assistants by students and staff, and the university's own scientific computing, in 4 published reports
The François Perroux lecture theatre at Université Jean Moulin Lyon 3, in May 2026. Photo Sebleouf, CC BY-SA 4.0, cropped, via Wikimedia Commons.
In the published reports of 4 universities, Grenoble Alpes, Strasbourg, Tours and Paris Dauphine, the use of AI assistants by students and staff accounts for 0.03 to 0.05% of reported emissions, according to our calculation at the world average electricity: about 0.36 kgCO2e per enrolled student per year. The computing that the university runs itself consumes far more electricity: in Grenoble, a single server room consumed 42 times more in 2024. None of the 4 reports names AI; it appears in electricity, equipment and purchases of services.
Contents
In Grenoble, the GRICAD mesocentre runs computing server clusters for the site's laboratories. In 2020, its CIMENT platform provided 24.9 million core-hours of computing, and its emissions report accounts for 128 tCO2e for the year, electricity and server manufacturing included. The IMAG room of the site's shared data centre, in the building that houses GRICAD, consumed 2,076 MWh in 2024, according to the annual footprint of the data centre. For the use of ChatGPT and other assistants by the 57,000 students and 6,130 staff of Université Grenoble Alpes, our calculation gives about 50 MWh per year: 42 times less than that one room.
Neither appears under the name of AI in the emissions reports that universities file on the ADEME platform. We opened those of 4 universities and set the use of assistants, estimated with the AI Impact Database, against each. The next infographic shows the result: 0.03 to 0.05% of each report for assistants; in Grenoble, 0.10% for the operation of the IMAG room in 2024 and 0.30% for the full report of the mesocentre in 2020.

Use of assistants accounts for 0.03 to 0.05% of the carbon footprint of 4 universities
The calculation starts from 2 profiles in the AI Impact Database, estimated task by task for typical use:
- a student who uses AI for their studies: 1.07 kWh per year, for explaining concepts, summarising articles, reworking assignments and preparing presentations;
- a researcher who uses it at work: 1.49 kWh per year. We apply it to all staff using the Database's convention for researchers, a use 2 times that of the average worker, of whom 25% use AI, which is half of that profile per staff member.
For students, we use the share measured by Eurostat: in 2025, 74% of French students had used generative AI for their studies in the previous 3 months. An enrolled student therefore accounts for 0.79 kWh per year, or 0.36 kgCO2e at the world average electricity (458 gCO2e/kWh), the value the hub uses when it is not known where the servers run.
| University, year of the footprint | Published footprint | Per student | AI assistants | Share of the footprint |
|---|---|---|---|---|
| Grenoble Alpes, 2024 | 42,365 tCO2e | 0.74 tCO2e | 22.7 tCO2e | 0.054% |
| Strasbourg, 2024 | 80,743 tCO2e | 1.47 tCO2e | 22.0 tCO2e | 0.027% |
| Tours, 2023 | 21,847 tCO2e | 0.83 tCO2e | 10.4 tCO2e | 0.048% |
| Paris Dauphine, 2024 | 8,544 tCO2e | 0.78 tCO2e | 4.3 tCO2e | 0.051% |
Footprints: ADEME, "Bilan GES" dataset, sum of the published items, method V5. Students: 57,000 (Grenoble Alpes, start of the 2024 academic year), more than 55,000 (Strasbourg, 2023-2024), 26,262 enrolled (Tours, 2022-2023), 11,000 in initial training (Paris Dauphine). Staff: headcount declared in each report. Assistants: our calculation, typical use, world average electricity.
Footprints of 0.74 to 1.47 tCO2e per student
Set against student numbers, these 4 footprints range from 0.74 to 1.47 tCO2e per student per year. Their scopes differ:
- Tours excludes food and waste;
- Grenoble counts students' journeys to their place of study, their internships and their international mobility;
- Strasbourg reports 33,537 tCO2e under commuting, 42% of its footprint.
In the 4 universities, students account for 90% of the assistants' electricity: the result follows their numbers far more than those of staff.
How much in intensive use?
If every user used AI like the most active tenth, with long tasks handed over end to end, the share would rise to 0.08 to 0.15%. To reach 1% of Grenoble's footprint, it would take about 19 times typical use. With servers in France, at the French mix in the Database (41 gCO2e/kWh), typical use would fall to 2.0 tCO2e in Grenoble instead of 22.7.
In Grenoble, one server room consumes 42 times the electricity of the assistants
What does a mesocentre consume?
A mesocentre is the computing centre of a university site, between a laboratory's servers and the national supercomputers. GRICAD's 2020 footprint counts the electricity of its servers, measured rack by rack, the manufacture of the servers spread over their period of use, then the journeys and workstations of its 24 full-time-equivalent staff:
- electricity of the servers and their cooling: 72 tCO2e, 56% of the total;
- manufacture of the servers: 39 tCO2e, 30%;
- journeys, missions, workstations and office electricity: 18 tCO2e.
CIMENT's share, 115 tCO2e, divided by its 24.9 million hours of computing, comes to 4.6 gCO2e per core-hour. The data centre also publishes its consumption: the IMAG room, which in 2025 hosted 29 tenants, IT services of institutions and laboratories, consumed 2,076 MWh in 2024, of which 1,647 for the servers themselves and the rest for cooling and facilities. The next head-to-head compares it with the use of assistants by the whole university: 2,076 MWh against 49.5, 42 times more for the room.
- 57,000 students, of whom 74% are users for their studies
- 6,130 staff
- 29 tenants in 2025, services and laboratories
- counted: cooling and facilities
In 2025 the site added a 300 kW room of servers dedicated to high-density computing and AI, that of GRICAD's Kraken platform, inaugurated in January 2026. The Grenoble institute for artificial intelligence, MIAI, financed 1.02 million euros of it over 2.55. At full load all year, these 300 kW would consume about 2,600 MWh, excluding cooling (our calculation, upper bound), 53 times the use of assistants.
In CO2, the gap narrows
The data centre counts its electricity with RTE's factor for France, 0.0199 kgCO2e/kWh in 2024. The operation of the IMAG room therefore emitted about 41 tCO2e that year (our calculation), 0.10% of the university's footprint if it is included in full. The assistants, whose servers are not known to be anywhere in particular, are counted at the world average, 23 times more carbon-intensive: 22.7 tCO2e. With 42 times less electricity, the use of assistants thus emits a little over half of what the room's operation does.
Manufacturing changes the order again: at GRICAD it makes up 30% of the 2020 footprint, because French electricity emits little. Estimates per hour of computing take this into account: about 1.5 gCO2e per core-hour and 40 gCO2e per GPU-hour in France, on examples from 2020, according to Gaël Guennebaud, of Inria, who points out that these values depend on how emissions are allocated between users. For an H100 GPU, the Database uses 900 Wh per hour: the year of study of a student who uses AI, 1.07 kWh, is worth a little over one hour of work for a single GPU.

None of the 4 reports names AI
A regulatory carbon footprint sorts emissions by item, not by use. A university's AI is spread across it according to who runs the servers, as set out in our method for counting AI in a Bilan Carbone® :
- assistant licences bought from a provider go to purchases of services, 11,637 tCO2e in Grenoble in 2024, 27% of the footprint;
- the university's computing servers go to electricity, 998 tCO2e in Grenoble, and, for their manufacture, to fixed assets, 8,770 tCO2e;
- free use of assistants by students and computing hours allocated free of charge on the national supercomputers have neither an invoice nor a meter at the university: a footprint that starts from spending and consumption does not see them.
Paris Dauphine is the only one of the 4 to say what it leaves out of digital:
However, these emissions from online digital services were not taken into account because they were small in order of magnitude compared with the rest of digital, and we had difficulty collecting this technical data (our translation).
Our calculation confirms this order of magnitude for assistants: 4.3 tCO2e at Dauphine, 0.05% of the footprint. Local authorities ask themselves the same question for their responsible digital footprint, which is covered in our guide.
Our view
In a university, AI is found first in its own server rooms and in the computing hours of its laboratories, which the footprints count without naming. For a company, the same calculation is done sector by sector. The use of assistants by students calls for a usage policy for data and teaching; in the carbon footprint, it weighs about half a thousandth. Before adding an AI line to the next footprint, the institution can ask itself 3 questions:
- How many computing hours do your laboratories consume, on your own servers and on the national supercomputers?
- Where are the assistants the institution provides served, and with what electricity?
- Does counting the use of assistants take more work than it weighs?
The use of assistants is an estimate by Projet Celsius: electricity of the servers and the data centre only, excluding manufacturing and the training of models. The footprints, headcounts and measurements of the Grenoble data centre cover different years and scopes; the university's published footprint does not make it possible to know whether the IMAG room and the GRICAD mesocentre, a unit shared by several institutions, are counted in it.

An engineer from Polytech Paris-Saclay and Bilan Carbone® methodology lead, he leads the carbon studies at Projet Celsius.
His page and articles →Contact him →LinkedIn ↗
An engineer from UTBM and life cycle assessment trainer at the Institut de Formation Carbone, he carries out the life cycle assessments at Projet Celsius.
His page and articles →Contact him →LinkedIn ↗Sources
11 documents
- ADEME, greenhouse gas emissions reports published on the ADEME platform, dataset "Bilan GES"2026entry 143
- GRICAD, Bilan GES GRICAD 2020, S. Chachay and F. Berthoud2021entry 592
- L. Azema, Bilan 2025 du datacentre grenoblois, séminaire annuel HDCG, 2 February 20262026entry 593
- GRICAD, Journée des utilisateurs 2025, plateforme de calcul Kraken et son financement, 6 November 20252025entry 594
- G. Guennebaud (Inria), Choix et limites des méthodes d'estimation de l'empreinte carbone des heures de calculs, Café Calcul, 4 June 20262026entry 595
- Projet Celsius, AI Impact Database, environmental database of artificial intelligence, engine 0.3.12026entry 144
- Eurostat, Usage des outils d'IA générative par les particuliers (isoc_ai_iaiu)2026entry 256
- Université Grenoble Alpes, 57,000 étudiantes et étudiants font leur rentrée, press release of 2 September 20242024entry 596
- Université de Strasbourg, dossier de presse de la rentrée 2024-2025, chiffres clés2024entry 597
- Université de Tours, Tableau de bord formation, établissement, 30 June 20232023entry 598
Every figure was read in its source; the hub's methodology is described in Methodology and sources.
Alexandre Veilly and Sébastien Pierfederici, How much does AI weigh in a university's carbon footprint?, AI Impact, Projet Celsius, 18 November 2026. https://projetcelsius.com/en/ai/analyses/ai-in-a-university-carbon-footprint/